• Revit

Making changes to mechanical systems

Make and review changes to connector configurations in a mechanical system.


Tutorial resources

These downloadable resources will be used to complete this tutorial:


00:05

The system classification

00:07

is again set to supply.

00:09

But the flow direction is now set to out at the

00:12

connector as the flow of air leaves the fan call unit.

00:17

We saw previously how the flow of all air

00:19

terminals was calculated at the fan core unit.

00:22

This is because the flow configuration of the supply

00:25

fan core unit connector is set to calculate it.

00:30

A review of the return connector shows the same arrangement.

00:37

Finally,

00:38

the size of the connector is associated to corresponding family

00:42

parameters in the same way as the air terminal connector

00:48

close the fan

00:49

unit firmly without saving the changes.

00:54

In summary, a change to flow rate at any of the air terminals on the system

00:59

will result in a change to calculated values at the fan call unit.

01:07

The piping arrangement shown in this view is made up of an air

01:10

handling unit with a preset water flow rate of five gallons per minute.

01:16

And a Chia

01:17

whose flow rate value is calculated from the air handling unit,

01:22

change the value at the air handling unit to 10 gallons per minute

01:26

and the value at the chiller will be the same

01:32

select each of the pumps in this arrangement and

01:35

note the flow rates through both of them.

01:37

It can be seen that the total value in the

01:39

system has been divided between the two but not equally

01:46

open the pump in the family editor and review the connector configurations,

01:54

select the incon connector and note the flow configuration is set to calculate it

01:60

because there is more than one pump.

02:01

The configuration must be set to system so that the user

02:05

can determine the proportion of flow going through each pump.

02:11

You will see the flow factor parameter has now become active.

02:15

A value can be set here or it can be set so

02:18

that the user can control the parameter from within the project.

02:23

Select associate family parameter

02:27

and then create a new parameter called flow factor.

02:36

Make this an instant parameter

02:39

and group it under mechanical flow.

02:43

Then close the dialog box

02:47

carry out the same procedure for the out connection on the pump

02:51

setting the connector configuration to system

02:56

and then associate the flow factor parameter

03:03

for each connector.

03:04

Select associate family parameter

03:08

against flow.

03:10

Then create a new instance parameter called chilled water flow

03:15

and group it under mechanical flow

03:29

select OK. To close all dialog boxes,

03:34

load the family back into the project and overwrite the existing.

03:41

Finally

03:42

enter the mechanical settings

03:45

and disable the option for closed loop piping networks.

03:53

The flow factor parameter is used to control the proportion of flow to each

03:57

pump and set to naught 0.5 will divide the flow equally between the two.

04:04

A review of the flow rates for the pipework in the system shows

04:07

the same distribution of the available flow set at the air handling unit.

04:15

In this video,

04:16

we have looked at the importance of the application of system connectors

04:20

and connector configurations for a range of elements in a mechanical system.

04:25

Correct application will ensure the accuracy of

04:27

information such as flow pressure and velocity

04:31

information that can be used to establish pipe and duct

04:34

sizes and to assess the suitability of associated mechanical equipment.

Video transcript

00:05

The system classification

00:07

is again set to supply.

00:09

But the flow direction is now set to out at the

00:12

connector as the flow of air leaves the fan call unit.

00:17

We saw previously how the flow of all air

00:19

terminals was calculated at the fan core unit.

00:22

This is because the flow configuration of the supply

00:25

fan core unit connector is set to calculate it.

00:30

A review of the return connector shows the same arrangement.

00:37

Finally,

00:38

the size of the connector is associated to corresponding family

00:42

parameters in the same way as the air terminal connector

00:48

close the fan

00:49

unit firmly without saving the changes.

00:54

In summary, a change to flow rate at any of the air terminals on the system

00:59

will result in a change to calculated values at the fan call unit.

01:07

The piping arrangement shown in this view is made up of an air

01:10

handling unit with a preset water flow rate of five gallons per minute.

01:16

And a Chia

01:17

whose flow rate value is calculated from the air handling unit,

01:22

change the value at the air handling unit to 10 gallons per minute

01:26

and the value at the chiller will be the same

01:32

select each of the pumps in this arrangement and

01:35

note the flow rates through both of them.

01:37

It can be seen that the total value in the

01:39

system has been divided between the two but not equally

01:46

open the pump in the family editor and review the connector configurations,

01:54

select the incon connector and note the flow configuration is set to calculate it

01:60

because there is more than one pump.

02:01

The configuration must be set to system so that the user

02:05

can determine the proportion of flow going through each pump.

02:11

You will see the flow factor parameter has now become active.

02:15

A value can be set here or it can be set so

02:18

that the user can control the parameter from within the project.

02:23

Select associate family parameter

02:27

and then create a new parameter called flow factor.

02:36

Make this an instant parameter

02:39

and group it under mechanical flow.

02:43

Then close the dialog box

02:47

carry out the same procedure for the out connection on the pump

02:51

setting the connector configuration to system

02:56

and then associate the flow factor parameter

03:03

for each connector.

03:04

Select associate family parameter

03:08

against flow.

03:10

Then create a new instance parameter called chilled water flow

03:15

and group it under mechanical flow

03:29

select OK. To close all dialog boxes,

03:34

load the family back into the project and overwrite the existing.

03:41

Finally

03:42

enter the mechanical settings

03:45

and disable the option for closed loop piping networks.

03:53

The flow factor parameter is used to control the proportion of flow to each

03:57

pump and set to naught 0.5 will divide the flow equally between the two.

04:04

A review of the flow rates for the pipework in the system shows

04:07

the same distribution of the available flow set at the air handling unit.

04:15

In this video,

04:16

we have looked at the importance of the application of system connectors

04:20

and connector configurations for a range of elements in a mechanical system.

04:25

Correct application will ensure the accuracy of

04:27

information such as flow pressure and velocity

04:31

information that can be used to establish pipe and duct

04:34

sizes and to assess the suitability of associated mechanical equipment.

Step-by-step guide

Make and review changes to connector configurations in a mechanical system.

  1. Open the project M04_01.rvt.
  2. Ensure that the current view is HVAC > Floor Plans > 1 – Mech.
  3. Select the VAV unit.
  4. On the contextual ribbon, click Edit Family to open it in the Family Editor.
  • The Revit interface, with the project for this example open to the 1 – Mech floor plan view, where the VAV unit is selected. On the ribbon, Edit Family is highlighted for selection.
  1. Select the connector at the front of the unit.
  • To the left, in the Family Editor, the front connector is selected on the VAV unit, and in the Properties palette on the right, the relevant parameters are listed.

In the Properties palette, note the following:

  • The System Classification parameter determines that the VAV unit can be connected to a supply air system.
  • The Flow Direction is set to OUT at the connector, meaning that the air flows out of the VAV unit.
  • The Flow Configuration is set to Calculated; the total flow rate for all air terminals connected to this equipment will be calculated at this point.
  • The connector size is associated with relevant family parameters, indicated by the small equals symbols next to the Height and Width fields.
  1. Close the family without saving the changes.
  2. Select the air handling unit as shown to confirm in Properties that the water flow rate is 5 GPM. This a preset value altered by the user.
  • In the floor plan view on the left, the air handling unit is selected, and in the Properties palette on the right, a Water Flow rate of 5 GPM is highlighted.
  1. Select the chiller as shown and confirm in Properties that the chilled water flow rate is also 5 GPM. This a calculated value determined by the flow rate entered at the air handling unit.
  • In the floor plan view, the chiller is selected.
  1. Select the air handling unit again.
  2. In Properties, change the Water Flow rate to 10 GPM.
  3. Select the chiller to confirm the updated value.
  • In the floor plan view on the left, the chiller is selected, and in the Properties palette on the right, the updated value of 10 GPM is highlighted in red.
  1. Select each of the pumps in turn and note the Calculated Flow rates.
  • In the floor plan view on the left, one of the pumps is selected, and in the Properties palette on the right, a Calculated Flow of 5.506 GPM is highlighted in red.

The total flow rate in the system is divided between the pumps, but not equally.

  1. Open the pump in the Family Editor.
  2. Select the IN connector.
  • The pump open in the Family Editor with the IN connector selected.
  1. Change the flow configuration to System and note that the Flow Factor parameter is now active.
  • In Properties, the Flow Configuration set to System, with the Flow Factor now active.

Associate the Flow Factor parameter, so that the value can be changed at the pump within the project:

  1. Next to the Flow Factor parameter value, click the small gray square.
  • In Properties, the pointer is hovering over the gray square next to the Flow Factor value, and the Associate Family Parameter tooltip is displayed to indicate that it will open if the gray square is clicked.

Since the required parameter does not exist, create a new one:

  1. In the Associate Family Parameter dialog box, click New Parameter.
  2. In the Parameter properties dialog box, enter a parameter Name, such as "Flow Factor".
  3. Select Instance.
  4. In the Group parameter under drop-down, select Mechanical – Flow.
  5. Click OK to close both dialog boxes.
  • The Parameter Properties dialog box, with the settings for the new Flow Factor parameter configured for this example, and with OK being selected.

Now, associate the new Flow Factor parameter with the OUT connector:

  1. On the pump, select the OUT connector.
  • The pump open in the Family Editor with the OUT connector selected.
  1. In Properties, change the Flow Configuration to System.
  2. Open the Associate Family Parameter dialog box.
  3. Select the Flow Factor parameter created in the previous step.
  4. Click OK.
  • The Associate Family Parameter dialog box, with the Flow Factor parameter created in the previous step selected and highlighted, and with OK being selected.

Next, create a chilled water flow parameter and associate the parameter for each connector:

  1. On the pump, select the IN connector.
  2. In Properties, next to Flow, click Associate Family Parameter.
  3. Click New Parameter.
  4. Name the new parameter "CHW-F", for chilled water flow.
  5. Select Instance.
  6. For Group parameter under, select Mechanical - Flow.
  7. Click OK to close both dialog boxes.
  • The Parameter Properties dialog box, with the settings for the new CHW-F parameter configured for this example, and with OK being selected.
  1. Select the OUT connector.
  2. Next to Flow, click Associate Family Parameter.
  3. Select the new CHW-F parameter.
  4. Click OK.
  5. To load the family back into the project, on the ribbon, click Load into Project.
  6. Select Overwrite the existing version.
  7. On the Systems tab, HVAC panel, click the Mechanical Settings dialog launcher.
  8. Deselect Enable analysis for closed loop hydronic piping networks.
  • The Mechanical Settings dialog box, with the Enable analysis for closed loop hydronic piping networks option deselected.
  1. Select each of the pumps to ensure that the new flow factor parameter is set to 0.5, which will divide the flow equally between the two.
  • In the Properties palette, the new Flow Factor parameter set to 0.5, and a new CHW-F parameter of 5 GPM.

A review of the new CHW-F parameter confirms that the total flow rate in the system is now equally divided between the two pumps.

  1. Select various sections of pipe in the system to confirm the even and correct distribution of the flow set at the air handling unit.
  2. Save the project.
Was this information helpful?